Answer:
[tex]\dot W = 1.667\, kW[/tex]
Explanation:
A well-sealed house means that there is no mass interaction between air indoors and outdoors. Hence, cooling process is isochoric. The heat removed by the air conditioner is:
[tex]\dot Q_{L} = \frac{m_{air}}{\Delta t} \cdot c_{v, air} \cdot (T_{o}-T_{f})\\\dot Q_{L} = \frac{800\, kg}{(30\, min)\cdot (\frac{60\, s}{1 \, min} )}\cdot (0.7 \frac{kJ}{kg \cdot K}) \cdot (15\, K)\\\dot Q_{L} = 4.667\, kW[/tex]
The power drawn by the air conditioner is:
[tex]\dot W = \frac{\dot Q_{L}}{COP_{R}} \\\dot W = \frac {4.667\, kW}{2.8}\\\dot W = 1.667\, kW[/tex]