Given Information:
ZΩ = 9 per phase
Sbase = 75 MVA
Sbase = 100 MVA
kV = 27 kV
kV = 30 kV
Required Information:
Zpu = ?
Zpu_new = ?
Answer:
Zpu = 0.925 pu
Zpu_new = 1 pu
Explanation:
Zbase = (kVbase)²/Sbase
Zbase = (27x10³)²/75x10⁶
Zbase = 9.72
Zpu = Zactual/Zbase
Zpu = 9/9.72
Zpu = 0.925 pu
Now base MVA is changed to 100 MVA and base kV is changed to 30kV so the per unit value becomes
Zbase = (kVbase)²/Sbase
Zbase = (30x10³)²/100x10⁶
Zbase = 9
Zpu_new = Zactual/Zbase
Zpu_new = 9/9
Zpu_new = 1 pu