Answer:
[tex]Q=41.33 KVAR\ \\at\\\ 480 Vrms[/tex]
Explanation:
From the question we are told that:
Voltage [tex]V=480/0 \textdegree V[/tex]
Power [tex]P=120kW[/tex]
Initial Power factor [tex]p.f_1=0.77 lagging[/tex]
Final Power factor [tex]p.f_2=0.9 lagging[/tex]
Generally the equation for Reactive Power is mathematically given by
Q=P(tan \theta_2-tan \theta_1)
Since
[tex]p.f_1=0.77[/tex]
[tex]cos \theta_1 =0.77[/tex]
[tex]\theta_1=cos^{-1}0.77[/tex]
[tex]\theta_1=39.65 \textdegree[/tex]
And
[tex]p.f_2=0.9[/tex]
[tex]cos \theta_2 =0.9[/tex]
[tex]\theta_2=cos^{-1}0.9[/tex]
[tex]\theta_2=25.84 \textdegree[/tex]
Therefore
[tex]Q=P(tan 25.84 \textdegree-tan 39.65 \textdegree)[/tex]
[tex]Q=120*10^3(tan 25.84 \textdegree-tan 39.65 \textdegree)[/tex]
[tex]Q=-41.33VAR[/tex]
Therefore
The size of the capacitor in vars that is necessary to raise the power factor to 0.9 lagging is
[tex]Q=41.33 KVAR\ \\at\\\ 480 Vrms[/tex]